2. Installation of power cables underground—In a coal mine serious damage was caused to a power cable underground. An enquiry into the incident revealed that a loaded tub on getting derailed had hit the cable, completely crushing the insulations and the sheath, and had resulted in a heavy flash. The cable had not been efficiently protected against mechanical damage as envisaged in Rule 122(a) of the Indian Electricity Rules, 1956. In view of the danger to the cables along haulage roads from run-away of tub derailments etc., there is always a possibility of the cable being damaged. Such an occurrence may lead to a serious situation particularly in a gassy and dusty mine.

It is, therefore, desirable that the installation of power cables along haulage roadways should be generally avoided. The cables should be installed along traveling or other roadways where roof and sides are adequately supported and there is good ventilation.

Wherever cables are installed, they should be so placed and secured as to ensure maximum protection against mechanical damage of all kinds, and particularly that due to their own weight, bending or twisting, traffic and ground movements. Damage to cables or crushing at points of their support should also be avoided. The supports for the cables should be spaced sufficiently close to prevent sagging.

(Cir. 15/1965)