Reg. 69 Guidelines for use of flame or electric welding or repairing apparatus in oil mines—In recent times a number of fires resulted due to welding operations at drilling and production installations. Oxy-acetelene or electric cutting and welding are not only fire hazards in oil mines but can also be source of health hazard due to toxic fumes or radiation. It is therefore essential that adequate precautions are taken and accordingly the guidelines given in Appendix are issued.

This is to request you to ensure that oxy-acelylene and electric cutting and welding operations are carried out in accordance with these guidance notes.

(Cir. Tech. 9/1982} APPENDIX GUIDELINES FOR USE OF FLAME OR ELECTRIC WELDING OR REPAIRING APPARATUS IN OIL MINES (ON SHORE)

1.0 Introductory Welding operation at drilling and production installations of oilfields can cause fire and health hazards unless adequate precautions are taken. These guidelines contain safeguards that should be adopted whenever name or electric welding and cutting operations are undertaken in oil mines. 2.0 Welders Only qualified welders, duly authorised by manager should be deputed for welding jobs. 3.0 Written Permit Before any welding or cutting work is undertaken at any installation, it shoutu be carefully inspected by the Engineer in-charge of the installation and he shall issue a written permit specifying therein the precautions to be observed and the procedure to be followed for carrying out the work. Copies of all written permits shall be entered in a bound-paged book kept for the purpose. 4.0 Test for inflammable vapour No welding or cutting work shall fie undertaken at any installation unless it has first been made safe and certified by a competent person appointed by the manager after testing with an approved gas testing apparatus to be safe and free from inflammable vapours, gas or liquids and is maintained in such condition, so long as the work is in progress. Copies of all such certificates shall be recorded in a bound paged book kept for the purpose.

5.0 Warning Signs In the immediate vicinity of the place where welding or cutting is undertaken, DANGER placards should be placed; CAUTION placards should be placed in such outlying areas as appear necessary. 6.0 Precautions against fire 6.1 All oils, oil-soaked earth, flammable substances should be removed from within and around the working area, 6.2 Matches, lighters, smoking apparatus and any other source capable of igniting inflammable vapour should not be permitted in the working area.

6.3 Adequate precautions should be taken to prevent fires being started by sparks, slag or hot metal.

6.4 At places where welding machines are operated by internal combustion engines, adequate ventilation should be provided to dilute the exhaust gases and the exhaust system should be provided with a suitable flame arrester to prevent emission of flame or sparks or discharge of heated particles.

7.0 Fire Fighting Equipment An adequate number of portable fire extinguishers capable of extinguishing oil fires should be kept ready for immediate use at places where welding is done. Welders and their helpers should be conversant with the use of such fire extinguishers.

8.0 Personal Protective Equipment Welders should wear fire-resistant protective clothing and equipment such as fire-resistant gloves, aprons, helmets and goggles with suitable filter lenses.

Where toxic or harmful fumes are likely to be produced as a result of welding, workers should be protected by respiratory protective equipment.

Where persons other than the welders are likely to be exposed to harmful radiations or sparks from electric arc welding they should be protected by screens or other effective means.

9,0 Welding in confined spaces When welding and cutting operations are being carried out in a confined space, adequate ventilation by mechanical means should be constantly provided to prevent accumulation of flammable vapours.

70.0 Welding on piping Before welding or cutting on piping which contained a flammable liquid or gas, the pipe should be disconnected or blinded. A closed valve should not be considered as a positive block. It is desirable to isolate, drain and purge the pipeline with inert gas or fill it with water before undertaking hot work.

Where vapour seals or plugs are utilised to prevent the escape of vapour from a pipeline, some positive method of venting or monitoring should be used to ensure against a pressure build-up in the line while hot work is in progress.

11.0 Supervision The Engineer in-charge mentioned at para 3.0 shall see that welding operations are carried out strictly in accordance with the written permit and the guidelines given above.

Reg. 75 GUIDELINES FOR USE OF ELECTRICAL EQUIPMENT IN HAZARDOUS AREAS IN OIL MINES 1.0 Introductory These guidelines aim at proper application of electrical equipment to avoid ignition of flammable vapours or gases in oilfields. 2.0 General Observations The following factors have been kept in view in framing these guidelines.

2.1 In an oilfield there is a possibility of accidental release of flammable liquid and natural gas, which will give rise to the presence of hazardous atmosphere, as defined later, at the following locations:

2.1.1 Drilling well consisting of well head, mud tank, mud trench, mud pumps, shale shaker, desander-desilter and degasser.

2.1.2 Producing oil and gas wells.

2.1.3 Group Gathering or Oil Collecting Stations or production- separation installations.

2.1.4 Flammable liquid storage tanks.

2.1.5 Gas Compressors and pumps, handling flammable liquids & gases.

2.2 Gases encountered at the aforementioned locations are sometimes heavier than air and when escaping into atmosphere will tend to spread outwards and downwards.

2.3 A mild air current may serve to extend the hazardous area in those directions of which gases might normally be carried; whereas a strong current of air may so accelerate the dispersion of gases that the extent of potentially hazardous areas would be greatly reduced.

2.4 In oilfield, ventilating conditions are generally favourable; most of the installations and well sites are in the open air, hence the extent of hazardous areas in many cases can be reduced.

2.5 In case of enclosed premises, the degree or probability of the presence of a hazardous atmosphere is more, as rapid dispersal of hazardous atmosphere cannot be expected due to lack of ventilation.

2.6 Standard of maintenance of equipment, operation and supervision influence the degree of probability of the presence of hazardous atmosphere at any installation.

2.7 The amount of special electrical equipment can be reduced by installing much of the equipment in less hazardous or safe areas, as far as practicable.

2.8 Persistent risk points—Examples of such sources of hazard are as follows:

2.8.1 Interior of pressure vessels and pipe containing gas air mixtures;

2.8.2 Free space above liquid level in tanks;

2.8.3 Free space immediately above open dipping, baths, etc.; and 2.8.4 The immediate vicinity of vapour exhausts and liquid outlets where these are designed to discharge as part of normal plant.

2.9 Occasional Risk Points—Examples of such sources of hazard are the immediate vicinity of mechanical glands and other localized spillage points and of vapour exhausts and liquid outlets designed to discharge only on plant malfunction.

2.10 Areas classified cover installed equipment under normal operations but in which abnormal conditions may exist for which there is practical protection to a degree commensurate with risk involved.

A possible catastrophe such as well blowout is not covered as it requires emergency measures at the time of occurrence. 3.0 Definitions 3.1 Hazardous Atmosphere—An atmosphere containing any flammable gas or vapour in a concentration capable of ignition.

3.2 Hazardous Area—An area where during normal operations, a hazardous atmosphere is likely to occur in sufficient quantity to constitute a hazard.

3.3 Safe Area—An area no part of which lies within a hazardous area.

4.0 Classification of Hazardous Area: [See IS: 5572 (Part-1) 1978]

To determine the type of electrical installation appropriate to a particular situation, the areas have been divided into three main zones, namely. Zone 0, Zone 1 and Zone 2, according to the degree of probability of the presence of hazardous atmosphere.

4.1 Zone 0 Areas—An area in which hazardous atmosphere is continuously present shall fall under this category. This classification is applicable only where it is expected that hazardous atmosphere will exist continuously. In the petroleum industry such a condition is rarely encountered except in confined spaces, such as the vapour space of closed process vessels, storage tanks or closed containers.

Since a hazardous atmosphere exists continuously, any arc or spark resulting from a failure of electrical apparatus installed in a Zone 0 area would almost certainly lead to fire or explosion.

Therefore, any installed electrical apparatus must afford a degree of protection as near as practicable to the absolute.

4.2 Zone 1 Areas—An area in which a hazardous atmosphere is likely to occur under normal operating conditions shall fall under this category. This classification is applied to areas in which a hazardous/atmosphere is likely to occur at any time and which, therefore, require the fullest practicable application of measures to prevent the occurrence of a hazardous electrical condition at any time and in any circumstances.

4.3 Zone 2 Areas—An area in which a hazardous atmosphere is likely to occur only underabnormal operating conditions shall fall under this category. This classifiction is applicable only where a fire or explosion hazard is unlikely and may be caused only by the simultaneous and improbable occurrence of an arc or spark resulting from an electrical failure and a hazardous atmosphere arising through failure of the conditions of control. It presupposes that any hazardous atmosphere resulting from an abnormal occurrence is rapidly dispersed so that possible contact with the electrical apparatus is of minimum duration. Any situation which allows a hazardous atmosphere to collect, such as pit or trench, although, it may be in the open are, shall in itself be classified as Zone 1 area, even though the surrounding area is classified as Zone 2.

5.0 Extent of Hazardous Area 5.1 Drilling Wells—Areas surrounding wells in the process of drilling or being serviced by drilling rigs should be classified as follows:

5.7.7 Well head area—(a) When the derrick is not enclosed and the substructure is open to ventilation, area above the ground level extending vertically 8 m above the well and horizontally 16 m in all directions from the well should be classified as Zone 2 area.

(b) When the derrick floor and substructure are enclosed, the entire enclosed substructure including cellars, pits, and sumps below the ground level should be classified as Zone 1 area but the area enclosed above the derrick floor should be classified as Zone 2 area.

(c) Any cellars, trenches, the pits belowground level and located in a Zone 2 area should be classified as Zone 1 area.

5.1.2 Mud Tank/Channel—(a) The area within a radius of not less than 8 m from a mud tank/channel located in the open air should be classified as Zone 2 area.

(b) The free space above the level of mud in tank/channel should be classified as Zone 1 area.

5.1.3 Mud Pump—The area surrounding a mud pump is unclassified unless it is located in an area that is classified because of some other installations.

5.1.4 Shale Shaker—(a) The area within a radius of not less than 4.5 m from the shale shaker located in the open air should be classified as Zone 1 area, while upto 8 m in all directions from the shale shaker should be classified as Zone 2 area.

(b) When the shale shaker is located in an enclosure, the area should be classified as Zone 1 to the extent of the enclosure.

5.1.5 Degasser—(a) The area surrounding a degasser is unclassified except for the vent, unless it' is located in an area that is classified because of some other installation.

(b) The open end of the vent from the degasser should be not less than 4.5 m above ground level; the area within a radius of 1.5 m from the open end of the vent extending in all directions should be classified as Zone 1; the area between 1.5 m and 3.0 m of open and of vent should be classified as Zone 2.

5.1.6 Desander-Desilter—The area within a radius of not less than 4.5 m from the desander-desilter located in the open air should be classified as Zone 2 area.

5.1.7 Effluent Pit/Open Sump—The area within a radius of not less than 8 m. from an effluent pit/open sump which contains flammable liquid should be classified as Zone 2. The free space above the level of flammable liquid in the pit/sump should be classified as Zone 1.

5.2 Producing oil and Gas Wells.

5.2.7 Flowing Well—(a) Area around a flowing well without any cellar and located in open air is unclassified.

(b) Area around a flowing well located in open area with a cellar, extending vertically upto 60 cm above the ground level should be classified as Zone 2, the collar should be classified as Zone 1.

5.2.2 Well under production test—(a) The area within a radius of not less than 16 m horizontally and extending 8 m vertically above from an open discharge of petroleum bearing fluid from a well under production test, should be classified as Zone 1 area.

(b) The area within a radius of not less than 16 m. horizontally and 8 m. vertically from a well under production test in a closed system should be classified as Zone 2 area.

5.2.3 Well-Pulling/Well Servicing Operation—The area within a radius of not less than 16 m. in all directions from a well-pulling and other such well servicing operation should be classified as Zone 1 unless tests with explosimeter made every two-hours show that hazardous atmosphere does not exist, in which case the area may be classified as Zone 2.

5.3 Oil and Gas Processing and Storage Equipment 5J.7 Maniflod—The area around a manifold located in open air on in a well ventilated shed is unclassified.

5.3.2 Oil-gas Separation Vessel/Protected Fired Vessel—(a) The - area within a radius not less than 8 m of any oil-gas separation vessel or any fired vessel protected from being a source of ignition and located in open air or in a well ventilated shed, operated as a closed system to prevent in normal circumstances the omission or accumulation of hazardous atmosphere should be classified as Zone 2 area.

(b) Any cellars, trenches or pits below ground level and located in a Zone 2 area should be classified as Zone 1 area.

5.3.3 Gas Vent—(a) The open end of gas vent should be not less than 4.5 m above ground level.

(b) The area within a radius of 1.5 m from the open end of the vent extending in all directions should be classified as Zone 1; the area between 1.5 m and 3.0 m of open end Should be classified as Zone 2 area.

5.3.4 Relief Valve—(a) The area within a radius of not less than 3 m of discharge of a relief valve, extending in all directions should be classified as a Zone 2 area.

(b) There should be no electrical equipment in direct path of discharge from a relief valve.

5.3.5 Pig Trap—The area within a radius of not less than 1.5 m of pig launching/receiving trap, extending in all directions should be classified as Zone 2 area.

5.3.6 Pump of Gas Compressor—-(a) Where a pump handling flammable liquids or a natural gas compressor is located in open air or well ventilated shed without walls, the area extending 8 m vertically above the source of hazard and 16 m horizontally in all directions should be classified as Zone 2 area. Beyond 8 m in the horizontal plane, the vertical extent of the hazardous area may be reduced to 8 m above the ground level.

(b) Pits, sumps, trenches below the ground level should be classified as Zone 1 area.

(c) Where such a pump or compressor is located in an adequately ventilated building, the entire interior of such building should be classified as Zone 2 area.

5.3.7 Storage Tank—(a) In the case of floating roof tank, the space above the roof and within the shell of the tank should be classified as Zone 1 area. The area surrounding the tank within 3 m from the tank shell, ends or roof and inside the enclosure upto top level of the enclosure wall should be classified as Zone 2 area.

(b) In the case of fixed roof tank, the area surrounding the tank within 3 m from the tank shell, ends or roof and inside the enclosure upto top level of the enclosure wall should be classified as Zone 1 area.

6.0 Selection of electrical equipment of hazardous areas Electrical equipment for Zone 0, Zone 1 and Zone 2 areas should be selected in accordance with guidance provided by Indian Standard IS: 5571-1979, the salient features of which are given in Appendix-I. In case of any doubt the matter should be referred to D.G.M.S. for decision.

7.0 Detection of hazardous atmosphere Explosimeter or other suitable gas testing apparatus should be kept available for testing the presence of a hazardous atmosphere in reasonable proximity to any hazardous area. Competent persons should be trained in the use of such apparatus. 8.0 Maintenance, Repair & Test Work. in classified zones Permits— No maintenance, repair or test work of electrical equipment should be undertaken in any classified zone unless such area has first been made free from hazardous atmosphere and a permit for work in form given in Appendix-2 is issued by the Electrical Engineer-in-charge of the installation or an electrical supervisor.

9.0 General Precautions 9.1 Power and lighting circuits installed in classified zones around a well-head, which are not essential for drilling and well-servicing operations, should be capable of separate isolation.

9.2 Master switches for controlling supplies to drilling rigs or well-servicing equipment should be located outside hazardous area at easily accessible places; these switches should be remotely operated from the driller's console.

References:.

(1) IS: 5572 (Part-1) 1978 Classification of hazardous areas (other than mines) for electrical installation.

(2) IS; 5571-1979 Guide for selection of electrical equipment for hazardous areas.

(3) API: BP 500B Classification of areas for electrical installations and drilling rigs and production facilities etc.

(4) Electrical Safety Code Institute of Petroleum, U.K.

(5) Petroleum Rules, 1976.

APPENDIX-I (See para 6.0 of the Guidelines)

Selection of electrical equipment for hazardous areas shall generally be made in accordance with IS: 5571-1979 Indian Standard Guide for Selection of Electrical Equipment for Hazardous Areas, the salient provisions of which are given here.

1. Selection of Type of Protection 1.1 Unless otherwise specified for particular equipment Table-1 shall be followed in the selection of type of protection of the electrical equipment for different zones of hazardous areas.

1.2 Procedure for Selecting Electrical Equipment 1.2.1 In order that electrical apparatus which is suitably protected may be selected for use in a particular hazardous area, the following information is necessary:

(a) The classification of the area that is the zone. [See IS: 5572 (Part-1) -1978)

(b) The lowest values of ignition temperature of the gas or vapour involved if more than one combustible gas or vapour is present.

(c) The characteristics of the gas or vapour involved in relation to:

(i) Ignition current or minimum ignition energy in the case of installation of intrinsically safe apparatus, or

(ii) Safe gap data in the case of installation of flame-proof enclosures.

1.2.2 The type of protection appropriate to the application should be selected according to the area classification as indicated in Table 2.

1.2.3 The maximum surface temperature of any unprotected surface of electrical equipment should not exceed the ignition temperature of the gas or vapour. For electrical apparatus ho margin of safety need be applied between maximum surface temperature and ignition temperature.

1.2.4 The permitted maximum surface temperatures have been classified as under:

Temperature Class Maximum Surface Temperature T 45°C T2 300°C T3 200°C T4 135°C T5 100°C T6 85°C A reference ambient temperature of 40°C is normally assumed unless otherwise indicated on the apparatus.

When deciding the maximum surface temperature for apparatus. Or the suitability of available apparatus which is to operate in an area endangered by a particular combustible, the maximum surface temperature of the T class of the apparatus Should not exceed the ignition temperature of the gas or vapour.

1.3 Portable apparatus 1.3.1 Portable hand lamps—Portable hand-lamps (whether self-contained or mains operated) shall be either flameproof or intrinsically safe. Torches shall be intrinsically safe and shall conform to IS: 5780-1970. They shall be designed in such a manner that hot filament ignition problem is avoided.

1.3.2 Telephone and other communication equipment and allied instruments in both Zone 1 and Zone 2 areas these shall be either of the intrinsically safe type or flameproof or increased safety type with sparkling parts enclosed in flameproof enclosure.

2.0 Installation requirements 2.1 Wiring Systems 2.1.1 Types of wiring and systems which may be used for installations in hazardous areas are:

(a) Cables drawn into screwed, solid drawn or seamless conduit, and

(b) Cables which are otherwise suitably protected against mechanical damage.

Requirements for the installation of power systems may not apply to the installation of apparatus and systems with type of protection ' 1'—intrinsic safety. For intrinsically safe circuits, there is normally no need to have special enclosures for the conductors. However, some protection will have to be afforded to such conductors primarily to prevent contact between conductors of intrinsically safe circuits and those of any other system, to avoid the possibility of arcing occurring at the point of contact or invasion of the intrinsically safe circuits by current arising from contact or electrostatic or electromagnetic induction. In addition, the conductors will have to be protected against mechanical damage.

The diameter of each strand of the conductor shall be not less than 0.300 mm. of copper or equivalent size of conductor specified in IS: 434 (Part-1) - 1964 or IS: 434 (Part-11) - 1964 in the case of aluminium conductor.

For (b) the following types of cables may be used in principle:

(i) Lead-sheathed and armoured cable;

(ii) Plastic or rubber-sheathed steel screen protected or armoured cable, with sheath overall;

(iii) Cable enclosed in a seamless aluminium sheath with or without armour, with an outer protective sheath;

(iv) Mineral insulated metal sheathed cable; and (v) Braided screen- protected flexible cables.

Unarmoured lead-covered cable is not acceptable. The sheath of a metal-sheathed cable should not be used as the neutral conductor.

2.2 Correctly designed terminations completed with armour clamps shall be provided for armoured cables. The armouring should be carried into the clamps to provide mechanical support to the cable and to ensure electrical continuity. Where such cable is lead covered and armoured, the lead sheath should be plumbed or mechanically gripped and sealed and the armouring should be carried over the lead joint.

2.3 Where circuits traverse a hazardous area in passing from one non-hazardous area to another, the wiring in the hazardous area should comply with the requirements of this standard.

2.4 Where practicable, contact, either deliberate or accidental, should be avoided between apparatus, conduit or cables, and any equipment or pipe work used for carrying combustible gases, vapours or liquids.

2.5 Where, owing to particular circumstances, contact between components referred to in 2.4 above is unavoidable, the armouring, conduit or sheathing of the cable should be bonded to the equipment or pipe work in such a manner and at such intervals as to ensure that under the worst fault conditions, the passage of any current will not give rise to incendive sparking or bring about a temperature rise approaching the ignition temperature of the combustible gas, vapour or liquid which may be present. Alternatively in the case of cable the insulation of the sheath may be sufficient to prevent danger.

2.6 Where cables or conduit pass through a floor, wall, partition or ceiling, the hole provided for them should be made good with cement or similar incombustible material to the full thickness of the floor, wall partition or ceiling, so that no space remains around the cable through which combustible gas liquid or vapour might spread. Alternatively cable glands may be used for this purpose.

2.7 Where trunking, duct, pipes or trenches are used to accommodate cables, precautions should be taken to prevent the passage of combustible gases, vapours or liquids from one area to another, and to prevent the collection of combustible gases, vapours or liquid in trenches. Such precautions may involve the sealing of trunking, dust and pipes, and the adequate ventilation or sand filling or trenches.

2.8 Where an overhead supply line is used for either power or telecommunication circuits, it should be terminated outside the hazardous area and be fitted at or near the terminal pole with an effective surge-protection apparatus. The cable used to connect the overhead line with the installation in the hazardous area should comply with the recommendations for wiring systems in hazardous areas. Conduit should not be used if it is likely to be subjected to vibration. The casing, armouring or sheathing should be electrically continuous and the end adjacent to the point of connection with the overhead line should be bonded to the earth electrode of the overhead line. In addition, the casing or sheathing should be electrically continuous and the end adjacent to the point of connection with the overhead line should be bonded to the earth electrode of the overhead line. In addition, the casing or sheathing should be independently earthed as near as possible to the junction of the cable with the installation and bonded to the earthing lead of any lightning-protective system associated with the hazardous area. If convenient, a common electrode may be used for this independent earth and for the lightning-protective system of the installation.

Where the overhead line supplying a building forming a hazardous area is supported by the building and the connecting cable to the installation consequently is short, the earth electrodes for the surge-protection apparatus on the overhead line may be used for earthing the cable sheath or casing and for any lightning- protective system associated with the hazardous area.

2.9 The wiring entry to the apparatus, direct or indirect should maintain the type of protection used.

2.10 Unused cable entries in electrical apparatus should be closed with plugs suitable for the type of protection used.

2.11 Factors affecting choice of wiring systems 2.11.1 Screwed steel conduit systems are satisfactory for many situations but should not be used where vibration might cause fracture or loosening of joints and where excessive stress may be imposed as a result of its rigidity or where corrosion or excessive internal condensation of moisture is likely to occur.

2.11.2 Lead-sheathed and armoured cables are suitable for underground installation. Steel-wire armour is preferred for underground use.

2.11.3 PVC-insulated and armoured cable, complying with IS:1554 (Part-1)

1967 with an extruded plastic outer sheath may be used for above ground or underground installation. Lead-sheathed cable should be used where spillages may affect integrity of the cable and/or allow migration of the liquid through the cable.

2.11.4 For telecommunication circuits, plastic-insulated and armoured telephone cables complying, where applicable, with the appropriate Indian Standard may be used.

2.12 Portable and Transportable Apparatus and its Connections:

2.12.1 Only certified portable electrical apparatus should be used in a hazardous area.

2.12.2 Apart from self-powered apparatus and from hand-lamps which shall meet the requirements of 2.12.3, earth-leakage protection, or earth monitoring, or both, should be included in the protection of the apparatus. Protection of the circulating- current type which automatically cuts off the supply in the event of the earth continuity conductor becoming disconnected, may, with advantage, be adopted as the earth-monitoring device.

2.12.3 Flameproof plugs and sockets should incorporate suitable electrical and/or mechanical means to prevent danger of ignition during the insertion or removal of the plug.

2.73 Flexible Cables 2.13.1 Flexible cables for portable and transportable apparatus may be protected by a polychloroprene, PVC or similar sheath, and may have an annular flexible metallic screen.

Where necessary, an additional earth continuity conductor should be incorporated. It should be insulated to the same standards as the live conductors, and should be incorporated within the cable sheath. The earth continuity conductor and screen should be bonded to the appropriate metal-work of the apparatus and to the earthing pin of the plug.

For portable and transportable apparatus with rated voltages not exceeding 1000 V (not exceeding 750 V for earthed direct- current systems) the supply cables should be heavy-duty type. , For portable apparatus with rated current and voltage, not exceeding 1.6 A and 250 V respectively, medium-duty supply cables may be used. The conductors should be of copper having a minimum cross-sectional area of 1.5 mm2.

NOTE—Flexible cables with aluminium conductors will not be permissible to be used in hazardous areas.

2.74 Automatic Electrical Protection 2.14.1 All circuits and apparatus in hazardous area should be provided with means to ensure disconnection quickly in the event of over-current, internal short-circuit or earth-fault conditions.

2.14.2 Protection and control apparatus shall be normally located in a non-hazardous area. Where its installations in a potentially hazardous area cannot be avoided, such apparatus should be provided with an appropriate type of protection.

2.15 Earthing and Bonding 2.15.1 Earthing should be in accordance with IS: 3043-1966. Efficient bonding should be installed where protection against stray currents or electrostatic charges is necessary.

TABLE 1: TYPES OF PROTECTION FOR DIFFERENT HAZARDOUS AREAS (Clause 4.1)

Zone of Hazardous Area Type of Protection Zone 0 No electrical equipment should be allowed. When this is not practicable intrinsically safe electrical apparatus categories 'la' and 'lb' and associated circuits should be employed Type of protection '1' Zone 1 Intrinsically safe circuits categories ('la' and 'lb') and associated apparatus- Type of protection '1'.

Flameproof equipment-Type of protection 'd'. Pressurized enclosures- Type of protection 'p'. Sandfilled apparatus-Type of protection 'q', Oil- Immersed apparatus- -Type of protection 'o'. Such other apparatus as may be specially certified or assessed for use in Zone 1 areas.

Zone 2 Intrinsically safe circuits categories 'ia' and 'ib' and associated apparatus— Type of protection 'i'.

Flameproof equipment—Type of protection 'e'. Pressurized enclosures— Type of protection 'p'. Sandfilled apparatus-Type of protection 'q', Oil- Immersed apparatus- -Type of protection 'o'. Non-sparking apparatus—Type of protection 'n'.

NQTE: For outdoor installations, the apparatus with type of protection 'e' and type of protection 'n' should be used with enclosures providing at least the following degree of protection ‘n’

(a) IP55 where there an unmsulated conducting parts internally, and

(b) IP 44 for insulated parts.

APPENDIX-2 Name of Mine...............................................................Owner................................................

Manager............................................

Permit for maintenance, repair or test work of electrical equipment in hazardous areas in oilfield Shri............................................................ and his co-workers named below are permitted to undertake the jobs mentioned later at .................................................

................................................on..............................„........from.......................................

MS (name of installation).... on.....(date)...from...........to...........hours on condition that following safety measures are complied with:

Job list and work procedure in brief:

Safety measures to be taken:

1. Tests for presence of hazardous atmosphere shall be made with explosimeter at every......hour interval.

2. No job shall be undertaken unless the area is made free from any hazardous atmosphere.

3. Dry-powder type fire extinguishers shall be kept available at the site.

4. The equipment should be effectively disconnected from the source of supply.

5.

6.

7.

8.

Names of co-workers:

1.

2.

3.

4.

Permit received (Shri.............................................) Electrical Engineer/Electrical Supervisor Signature with date incharge Designation:

Signature with date

2. Provision of lightning assestors in permanent installations—There was an incidence of fire at an oil collecting station in an oil field under the following circumstances:

There was thunderstorm with flashes of lightning in the locality. At this time the oil level in the oil tank stood at 2.6 metres. Excess gas from within the tank was being released though vents provided at the top of the tank. The gas consisted of a mixture of Propane, Butane and Pentane having a specific gravity of 1.3. Because of the higher density, the gas had a tendency to settle around the top of the tank and diffusion was slow.Suddenly the lightening struck at the top of the tank and the gas escaping through the vent was ignited. Soon the fire spread over a 3 m wide area around the vents. The flame was about 2.8 m high. Steps were taken to control the fire which was brought under control within about half an hour time.

During the enquiry into the cause of any circumstances leading to the fire it was observed that although the storage tanks were properly earthed, there were no lighting arresters provided within the installation area. Since there was no safe path provided in the area for diverting to earth any electrical surges due to lighting, it struck the 10 m high metallic storage tank standing in the open and ignited the gas.

In order to avoid such type of dangerous occurrences, at all permanent installations where natural gas is released or is likely to be released to the atmosphere in hazardous quantities suitable lightening arresters should be provided within the installation area to prevent danger due to lightening.

The permissions already granted under the Oil Mines Regulations, 1922 shall be deemed to have been modified to require the provision of such lightening arrestors.

(Cir. 24/1971)

Reproduced from the official DGMS circular compilations for public reference. The PDF is the authoritative text; DGMS may have amended or withdrawn older instructions since.