Cir. 38/1973

Requirement regarding electrical apparatus in mines where fire exists in a seam of Degree I gassiness

Department
Not stated
Year
1973
Collection
Regulation-wise digest (to 2017)
Under
Rule 126
In the DGMS Circulars (up to June 2017) compilation, p. 647.
Open PDF at page 647

4. Requirement regarding electrical apparatus in mines where fire exists in a seam of Degree I gassiness— Occurrence of fire in some of the Degee I gassy seams has indicated that concentration of inflammable gas in the vicinity of fire areas may sometimes be such as to be comparable to that in case of a Degree II gassy seam. If such a condition of gassiness is created by virtue of fire, use of non-flameproof electrical equipment close to the firey area is not admissible. Therefore whenever there is fire in a Degree I gassy seam, accumulation of gas at the sites of electrical equipment near the fire area shall be systematically checked and if an accumulation in the general body of air close to the non flameproof equipment is found to exceed 0.5%, all non-flameproof equipment shall be forthwith disconnected from supply. All flameproof electrical installations shall be used in such areas in compliance with Rule 126 of the Indian Electricity Rules, 1956. Needless to say, supply of current to cables and apparatus in the fire area and its immediate vicinity should be cut off whenever occurrence of fire is detected in any seam.

(Cir. 38/1973)