Cir. 64/1964
Flameproof apparatus approved for use in gassy mines
- Department
- Not stated
- Year
- 1964
- Collection
- Regulation-wise digest (to 2017)
- Under
- CMR 181
3. Flameproof apparatus approved for use in gassy mines—According to the standard specifications for flameproof enclosures of electrical apparatus adopted in different countries including U.K. and India, apparatus approved for use in one group of gases is not necessarily permissible for use in another group unless the equipment is certified and approved by the recognised authority for use in both the Gas Group atmospheres.
The main objection to the use in coalmines of flame-proof electrical equipment certified for groups of gases other than Gas Group I lies in the type of cable intended to be used. What is designed exclusively for Gas Group II and/or Gas Group III may not admit of the attachment of a cable sealing and dividing box to the terminal box of the said flame-proof equipment for use in gassy coal mines. Again, what is designed and approved for the three groups of gases, namely Group I, Group II and Group III might be delivered to the users with. a cable attachment which is not suitable for use in mines.
It is therefore necessary that correct type of flameproof equipment should be obtained for use in gassy mines and to do so it should be clearly specified while ordering for such equipment that the equipment must be certified/approved for Gas Group I and provided with cable sealing and dividing box/boxes suitable for the particular type of cable used in the mines. Similarly in the case of portable or transportable apparatus, the type and size of the flexible trailing cable intended to be used with the apparatus should be intimated to the suppliers so that suitable flame proof connector for the cable is supplied with the apparatus.
For the flame proof equipment certified only for Gas Group II and/or III which are already in use in gassy mines, it is advisable to check up and see that the cables are attached to the terminal box of the apparatus concerned using cable sealing and dividing box/boxes designed and manufactured for use with the equipment. It should also be ensured that the attachment of a cable sealing and dividing box to the box of a flame-proof equipment is in properly designed flameproof joint. If this is not done immediately, such apparatus should be withdrawn from the mine.
(Cir. 64/1964)