Cir. Tech. 2/1989
Managements are aware that the Indian Electricity Rules 1956 now permit transmission of energy at voltage not…
- Department
- Technical
- Year
- 1989
- Collection
- Regulation-wise digest (to 2017)
- Under
- Rule 122
Rule 122
1. Jointing of High VoltageCabIes—1. Managements are aware that the Indian Electricity Rules 1956 now permit transmission of energy at voltage not exceeding 11000 volts and its use at voltage not exceeding 6600 volts in mines.
2. The use of high voltage cables in coal mines consequently to deployment of higher horsepower machines is consistently on the increase. The cables need greater care and vigilance in respect of their installation and maintenance.
3. One of the important design features of high voltage cables as against medium voltage cables is the provision of screening immediately over the power conductors as well as the conductor insulation. The table shows the requirement of screening for paper, poly venyle chloride (PVC) and cross-linked polyethylene (XLPE) insulated cables for 3300 volts and above, as per relevant Indian Standard Specifications.
4. Jointing of high voltage cables provided with core screening requires skill and expertise.
The semi-conductive (non-metallic) core screening is required to be scraped over certain length of the core and the exposed core insulation thoroughly washed and taped. The joint is then sealed by high voltage filling compound, compatible with insulating material of the cable used.
5. There was a dangerous occurrence in the recent past wherein improperly made 6.35/1 KV PVC insulated cable joints in one of the mines burst and damaged the cable connectors. The joints had been without the removal of outer semi-conductive screening. Further the joints were sealed by hot pouring compound, transported from surface to underground site, in an open bucket. The possibility of contamination of compound with water dripping from roof could not be ruled out. The cable was energised without sealing the joints and later after sealing them over though the insulation resistance tested by a high voltage insulation tester was not satisfactory. In both cases, the joints failed soon after energisation of cable. Cable joints were subsequently got made under the guidance and supervision of a cable jointer deputed by the cable manufacturer.
Some of staff from the mine have also been trained at the cable manufacturer's works and are now able to make joints on high voltage cables confidently.
6. Attention of all those connected with cable installation and maintenance works should be drawn to the aforesaid incident and action initialed to get such personnel trained in the technique of jointing high voltage cables. Such facilities •are available with most of reputed cable manufacturers.
Annexure Table showing provision of conductor and core screening for paper, PVC and XLPE insulated cable for working voltages of 3.3 KV and above as per Indian Standard Specifications.
Sl.
No.
IS Specification Voltage Grade Conductor Screening and its Type Core Screening and its type 1.
IS 692-1973 Paper 12.7/22 KV 6.3/11 KV and above for single core and insulated cable above conduct!
metallic)
12.7/22 KV and above for 3 core, semi conductive (non-metallic or conductive metals nonmagnetic).
IS 1554-PartII 1970 PVC insulated cable 3.9/3.3 above semi conductive (Non-metallic)
6.3/11 KV and above conductive metallic, nonmagnetic) even semi- conductive (non-metallic).
3.
IS709- PartII1973 XLPE insulated cable.
3.3/3.3 above semi conductive (non-metallic)
3.3/3.3 KV and above conductive (metallic, nonmagnetic) over semi conductive (non-metallic).
(Cir. Tech. 2/1989)