Skip to content

Cir. Tech. 3/1989

Accidents on overhead lines and sub-station structures

Department
Technical
Year
1989
Collection
Regulation-wise digest (to 2017)
Under
Rule 36
In the DGMS Circulars (up to June 2017) compilation, p. 641.
Open PDF at page 641

2. Accidents on overhead lines and sub-station structures—Overhead lines and sub-station structures continue to claim precious lives of skilled and semi-skilled personnel in the mining industry.

In two separate accidents, in the recent past, two skilled person went atop overhead line supports after the supply was stated to have been switched-off. As they commenced work and came in contact with bare conductors of the overhead line, they received shock and fell down and sustained serious injuries. One of them later died in hospital. These accidents could have been prevented had the overhead line conductors been discharged and earthed before commencing work as required under Rule 36(1) of Indian Electricity Rules, 1956. The simple precaution not only dissipates residual energy in the system to ground but also draws the attention of work persons if the system remains live inadvertently. It also eliminates the possibility of shocks from induced voltages and accidental charging of lines from either end while work is in progress.

The above incidences apparently underscore the need for improved safety management while at work on over-head line system.

The attention of electric engineering staff may be drawn to the aforesaid accidents and it may be ensured that work on overhead line conductors and other electricals is taken up only after they have been discharged and effectively earthed. This elementary precaution will go a long way in preventing such tragic accidents which have been occurring with disquieting regularity year after year.

(Cir. Tech. 3/1989)

Reproduced from the official DGMS circular compilations for public reference. The PDF is the authoritative text; DGMS may have amended or withdrawn older instructions since.