Cir. Tech. 5/1983

Use of electrical equipment in hazardous areas in oil mines

Department
Technical
Year
1983
Collection
Regulation-wise digest (to 2017)
Under
Reg. 75
In the DGMS Circulars (up to June 2017) compilation, pp. 673–674.
Open PDF at page 673

3. Use of electrical equipment in hazardous areas in oil mines—Guideline for use of electrical equipment in hazardous areas in oil mines is enclosed for your information and necessary action.

The Indian Oil Mines Regulations 1933 are being revised and it is proposed to make the following provisions regarding use of electrical equipment in hazardous areas:

(1) No electrical equipment including lighting apparatus shall be used in Zone '0' hazardous area.

(2) In every Zone '1' hazardous area only intrinsically safe and flameproof electrical apparatus and equipment shall be used.

(3) In every Zone '2' hazardous area only flameproof or increased safety or pressurised electrical apparatus and equipment or such other electrical equipment as may be approved by the Chief Inspector of Mines shall be used.

In the interest of safely, it is desirable that till such time that the Oil Mines Regulations are revised, these guidelines may be kept in view while using electrical equipment in hazardous areas in oil mines.

(Cir. Tech. 5/1983)

Reproduced from the official DGMS circular compilations for public reference. The PDF is the authoritative text; DGMS may have amended or withdrawn older instructions since.