No. DGMS(Tech) Circular No.8 of 2006 Dhanbad, dated 28.12.2006 To The Owner, Agent and Manager of all mines and All Manufacturers of Electrical Equipment.

Sub:

Setting value of Earth Leakage/Fault relays with restricted neutral system of supply in belowground mines, oil mines and opencast mines.

1. With the amendment of sub clause 1 of Rule 116 of the Indian Electricity Rules, 1956, it is mandatory that earth fault current shall not be more than 750 milli-ampere for system voltages upto 1100 V in respect of belowground mines and oil fields and not more than 50 amperes in 3.3 KV/6/6V system in opencast mines. To limit the magnitude of earth fault current, restricted earthed neutral system of supply need to be employed.

2. By restricting the prospective earth fault current to the values mentioned above, adequate tripping ratio between the prospective earth fault current and operating value of earth leakage relay is necessary to ensure that sufficient earth fault current is available for detection, when an earth fault occurs.

3. When a cable, connected to a typical mining supply system is subjected to a two phase short circuit and earth fault, the voltage available to drive earth fault current is reduced by upto 68% particularly when the system is supplying a large motor load at the time the fault occurs. Fault current flowing to earth is not more than 110 milli- ampere in such condition.

4. Hence, to ensure operation of earth fault protection under conditions of two phase short circuit and earth fault with a large connected motor load, it is necessary to employ a tripping ratio of at least 7:1.

5. To ensure operation of earth fault protection for a ground fault of a Delta/Star transformer covering 90% of the star connected winding, a tripping ratio of 10:1 is necessary.

6. The tripping value, thus selected shall be above the system charging current. The system charging current is the fault current that will flow when one phase is faulted in an isolated neutral/free neutral system of supply.

7. Considering the above, the standard practice is to set the tripping value of all the earth leakage/fault relays between 80-100 milli-ampere for belowground and oil mine installations for a system voltage upto 1100V and between 5 to 7 amperes in 3.3KV/6/6KV system in opencast mines.

8. With the above tripping value, selective relaying cannot be achieved by increasing the operating value of upstream earth leakage/fault relays, but can only be accomplished by increasing the operating time of upstream relays. By doing so, if the tripping mechanism of the GEBs or field switches or the intermediate switchgears fails to operate, the main breaker of the transwitch unit/transformer will be tripped after a short delay.

9. It is therefore, necessary to ensure that:

a. Tripping value of all the earth leakage/fault current shall be set between 80 to 100 milli-ampere for belowground installations with a clearance time less than 600 millisecond for transwitch unit/transformer secondary main, less than 400 millisecond for intermediate switchgears and less than 200 millisecond for the Gate End Boxes and the switchgears controlling drills panels.

b. Tripping value of all the earth leakage/fault relay shall be set between 80-100 milli-ampere for oil mines, with a clearance time less than 600 millisecond for the transformer secondary main, less than 400 millisecond for the switchgears controlling motor starters, and c. Tripping value of all the earth leakage/fault relays shall be set between 2 to 5 amperes for opencast mines, with a clearance time less than 600 millisecond for the transformer secondary main, less than 400 millisecond for intermediate switchgears and less than 200 millisecond for the field switches.

10. Earth leakage relays incorporated with electrical apparatus used in belowground mines and oil mines for a system voltage upto 1100V, shall have current settings from 50 to 250mA having set values at 50mA, 80mA, 100mA, 150mA, 200mA and 250mA with time lag between 0 to 1 sec, in steps of 100ms.

11. Earth leakage relays for opencast mines shall be of core balance transformer operated relays having current settings between 2 to 5Amps with time lag between 0 to 1 sec in steps of 100 ms.

12. Further, neutral resistance monitoring relay shall be incorporated with every transformer/transwitch unit to prevent the shifting of restricted earthed neutral system of supply to isolated neutral system of supply, in case of resistance fails.

It is needless to mention that earth leakage relays, resistance and resistance monitoring relay shall be of high quality and subjected to relevant tests as per the relevant Indian Standard or IEC to ensure satisfactory performance.

<><><><><>

Reproduced from the official DGMS circular compilations for public reference. The PDF is the authoritative text; DGMS may have amended or withdrawn older instructions since.